American Standard HVAC YCZ036F1/3MOA Manual

The American Standard YCZ036F1/3MOA is a high-efficiency, single-stage, 3-ton residential gas furnace with a variable-speed blower motor, designed for upflow/horizontal installation. It features a durable aluminized steel heat exchanger, electronic ignition, integrated diagnostic controls, compatibility with various thermostats, and multi-speed airflow adjustment. Rated at 36,000 BTU/hr input with 96% AFUE efficiency. Below are key sections for safety, features, installation, setup, operation, maintenance, and troubleshooting.

1. Features at a Glance 2. Installation Requirements 3. First-Time Setup & Startup 4. Specifications 5. Controls and Settings 6. Connecting Thermostat & Power 7. Operating Instructions 8. Maintenance Procedures 10. Regulatory Information 11. Troubleshooting

Features at a Glance

Key components: Aluminized steel primary heat exchanger, Variable-speed ECM blower motor, Hot surface ignitor, Integrated control board with diagnostic LED, Multi-tap transformer, Flue outlet, Condensate drain connection, Gas valve with manual shutoff.

FeatureDescription
Heat ExchangerDurable aluminized steel construction
Blower MotorVariable-speed ECM for quiet operation and efficiency
Ignition SystemElectronic hot surface ignitor (no standing pilot)
Control SystemIntegrated board with status LED for diagnostics
Vent Connection3" PVC flue outlet for sidewall or roof venting
Drain Connection3/4" PVC condensate drain port
Gas ValveIncludes manual shutoff and regulator
AirflowMulti-speed settings adjustable via motor taps
FilterStandard 1" or optional 4" media filter cabinet
Safety DevicesLimit switches, pressure switch, flame sensor

Installation Requirements

Unpack and inspect unit for shipping damage. Ensure location meets clearance and venting requirements.

  1. Location: Install in a clean, dry area with minimum clearances: 1" sides/rear, 24" front (service), 6" above unit.
  2. Venting: Use approved PVC pipe for intake and exhaust. Maintain proper slope away from furnace.
  3. Gas Supply: Connect to 1/2" black iron pipe. Test for leaks with soap solution. Gas pressure must be set per rating plate.
  4. Electrical: Provide dedicated 120V, 15A circuit. Connect line voltage to unit junction box. Connect 24V thermostat wires to control board.
  5. Drain Line: Install 3/4" PVC condensate line with trap, pitched to drain.
  6. Ductwork: Seal all connections to prevent air leakage. Ensure return air duct is properly sized.

WARNING! Installation must comply with all local codes and ordinances. Gas fitting and electrical work should be performed by qualified technicians.

First-Time Setup & Startup

After installation, perform initial setup and verification before regular operation.

  1. Pre-Start Check: Verify gas supply is on, electrical power is connected, thermostat is set to OFF, and filter is clean and installed.
  2. Gas Pressure Check: Using a manometer, verify inlet and manifold pressures match specifications on rating plate.
  3. Blower Speed Setting: Select appropriate cooling and heating speed taps on the control board based on external static pressure and required CFM.
  4. Startup Sequence: Set thermostat to HEAT mode and temperature above room temp. Observe ignition sequence: inducer motor on, pressure switch closes, hot surface ignitor glows, gas valve opens, flame established.
  5. System Check: Verify proper flame, check for unusual noises, measure temperature rise across heat exchanger (should be within range on rating plate).

CAUTION! Do not bypass safety controls. If furnace fails to start or locks out, refer to diagnostic LED and troubleshooting section.

Specifications

Controls and Settings

Primary control is via the integrated furnace control board and the wall thermostat.

Control Board: Located behind the lower access panel. Features a diagnostic LED that flashes error codes. Includes terminals for 24V thermostat connections (R, W, G, Y, C) and blower speed taps (COOL: HI/LO/MED, HEAT: HI/LO/MED).

Thermostat: Compatible with most single-stage heat/cool thermostats. For optimal performance, a programmable thermostat is recommended.

Blower Speed Adjustment: Change heating or cooling airflow by moving the wire to a different speed tap on the control board. Refer to installation manual for CFM charts based on external static pressure.

Gas Pressure Adjustment: Performed at the gas valve regulator using a manometer. Do not adjust unless qualified.

Connecting Thermostat & Power

  1. Turn OFF electrical power to the furnace at the disconnect switch or circuit breaker.
  2. Remove the furnace access panel to expose the control board.
  3. Run 18-gauge thermostat wire from the furnace location to the thermostat. Minimum 5-wire (R, W, G, Y, C) recommended.
  4. Connect wires to the corresponding terminals on the control board: R (24V Hot), W (Heat), G (Fan), Y (Cool), C (Common).
  5. Connect the other end to the thermostat sub-base following its wiring diagram.
  6. Connect the 120V line voltage (Black-Hot, White-Neutral, Green/Bare-Ground) to the furnace junction box.
  7. Restore power and verify operation.

Tip: Use a level when mounting the thermostat. Ensure the C (common) wire is connected for proper operation of smart thermostats.

Operating Instructions

Operation is controlled by the wall thermostat.

  1. Heating Mode: Set thermostat to HEAT and desired temperature. The furnace will initiate its startup sequence when room temperature falls below the setpoint.
  2. Cooling Mode (with AC): Set thermostat to COOL. The 'Y' terminal energizes, starting the outdoor condenser and the furnace blower at the cooling speed.
  3. Fan Only Mode: Set thermostat to FAN ON. The 'G' terminal energizes, running the blower continuously at a low speed for air circulation.
  4. Shutdown: To turn off heating or cooling, set thermostat system switch to OFF. The fan may continue to run for a post-purge period.

WARNING! Do not attempt to adjust the gas valve or control board settings while the furnace is operating. Keep flammable materials away from the furnace.

Maintenance Procedures

Regular maintenance ensures efficiency, safety, and longevity.

  1. Monthly: Check and replace the air filter if dirty. A clogged filter reduces airflow and efficiency.
  2. Annually (Before Heating Season): Have a qualified technician perform:
    • Inspect heat exchanger for cracks or corrosion.
    • Clean flame sensor with fine emery cloth.
    • Check and clean burners.
    • Inspect inducer motor and wheel.
    • Check all safety controls (limit switches, pressure switch).
    • Verify gas pressure and combustion analysis (CO levels).
    • Clean condensate trap and drain line.
    • Check and tighten all electrical connections.
  3. General: Keep area around furnace clean and free of debris. Ensure vent terminations are clear of obstructions like snow or leaves.

CAUTION! Always turn off electrical and gas supply before performing any maintenance. Only qualified personnel should service the gas and electrical components.

Regulatory Information

This appliance is design-certified for use in the United States and Canada. It complies with ANSI Z21.47/CSA 2.3 standards for gas-fired central furnaces. Installation must conform with local building codes, and in the absence of local codes, with the National Fuel Gas Code (NFPA 54/ANSI Z223.1) or CAN/CGA B149 Installation Codes. The furnace contains safety devices which must not be bypassed. For technical support or to locate a dealer, visit www.americanstandardair.com or contact American Standard Heating & Air Conditioning at 1-800-526-2200.

Troubleshooting

SymptomPossible CauseCorrective Action
Furnace will not startNo power, thermostat set wrong, gas valve off, door switch open.Check circuit breaker, thermostat settings, gas valve position, ensure access panels are secure.
Blower runs but no heatIgnition failure, gas supply off, faulty gas valve or ignitor.Observe diagnostic LED flash code. Check for gas supply. Verify ignitor glows. Call for service if lockout occurs.
Furnace short cycles (turns on/off frequently)Dirty filter, restricted airflow, high limit switch tripping.Replace air filter. Check for blocked vents/registers. Ensure blower speed is set correctly.
Unusual noises (banging, rumbling, squealing)Dirty burners, loose components, inducer or blower motor issues.Turn off furnace. Have technician inspect and clean burners, tighten mounting hardware, check motors.
Diagnostic LED flashing a codeInternal fault detected by control board.Count the number of flashes, then refer to the fault code chart on the inside of the access panel or installation manual.
Condensate drain leaking or cloggedAlgae growth, improper trap installation, frozen drain line.Clean trap and drain line with approved cleaner. Ensure trap is properly primed and line is pitched to drain. Insulate if in cold space.

Reset Procedure: If the control board is in lockout (LED flashing a code), turn off power to the furnace at the disconnect or breaker for 30 seconds, then restore power. The furnace will attempt to restart. If the problem persists, call for service.

Service: For all repairs not covered in this guide, contact a qualified HVAC technician. American Standard dealer locator: www.americanstandardair.com or 1-800-526-2200.

American Standard HVAC YCZ036F1/3MOA Manual © - All Rights Reserved 2025