American Standard HVAC YCC060F-M Manual

The American Standard YCC060F-M is a high-efficiency, single-stage, 5-ton residential condensing unit designed for outdoor installation. It features a WeatherArmor™ Ultra protection system, Spine Fin™ coil technology, Climatuff™ compressor, and compatibility with American Standard communicating thermostats for enhanced comfort control. Below are key sections for safety, features, installation, setup, operation, and troubleshooting.

1. Features at a Glance 2. Installation 3. First-Time Setup & Startup 4. Specifications 5. Controls and Settings 6. Connecting to Thermostat & Indoor Unit 7. Operation & Maintenance 8. Diagnostics & Alerts 9. Care & Cleaning 10. Regulatory Information 11. Troubleshooting

Features at a Glance

Key components: Durable outdoor cabinet with Spine Fin™ coil, Climatuff™ compressor, single-speed fan motor, high and low pressure service ports, and electrical connection box.

FeatureDescription
WeatherArmor™ Ultra CabinetGalvanized steel with baked-on powder paint for corrosion resistance
Spine Fin™ CoilCopper tubing with aluminum spines for efficient heat transfer and durability
Climatuff™ CompressorReliable, single-stage compressor with sound insulation
Single-Speed Fan MotorPermanent split capacitor (PSC) motor with weather-resistant design
Service ValvesHigh and low pressure ports for system charging and diagnostics
Electrical Connection BoxConveniently located with terminal block for power and control wiring
Sound InsulationInternal compressor blanket for quiet operation
CompatibilityDesigned to match with American Standard indoor coils and furnaces
RefrigerantR-410A
Safety ControlsHigh and low pressure switches, internal overload protection

Installation

Unpack and inspect unit for shipping damage. Select a suitable outdoor location.

  1. Location: Place on a level, stable pad (concrete or composite) with minimum 24" clearance on all sides, 60" above unit, and 48" from rear for service.
  2. Electrical Connection: Disconnect all power. Run properly sized copper conductors from disconnect to unit terminal block (L1, L2). Install a fused disconnect per NEC codes.
  3. Refrigerant Lines: Connect approved, clean, dehydrated refrigerant linesets to indoor coil. Brazing must be done with nitrogen purge.
  4. Condensate Drain: Ensure indoor coil drain line is properly installed and trapped.
  5. Thermostat Wiring: Run low-voltage control wire (minimum 18 AWG) from indoor unit/furnace to outdoor unit control terminal block.

WARNING! Installation and servicing of refrigerant circuits must be performed by a qualified technician in accordance with safety codes. Unit contains high voltage. Disconnect all power before servicing.

First-Time Setup & Startup

After installation is complete, perform initial system startup and checkout.

  1. Pre-Start Check: Verify all electrical connections are tight. Ensure refrigerant lines are connected, leak-checked, and properly insulated.
  2. Power On: Restore power at disconnect and indoor unit.
  3. Thermostat Setup: Set thermostat to OFF. Configure thermostat settings (system type: conventional, fan: AUTO).
  4. Startup & Charging: Set thermostat to COOL, temperature below room temp. Unit should start. Measure superheat/subcooling and adjust refrigerant charge per manufacturer specifications using manifold gauges.
  5. System Check: Verify correct airflow across indoor coil, check temperature drop (typically 15-20°F), listen for abnormal noises, and ensure condensate is draining.

CAUTION! Do not operate unit without correct refrigerant charge. Overcharging or undercharging can damage the compressor.

Specifications

Controls and Settings

Primary control is via the compatible thermostat. Unit has an integrated control board with LED diagnostic light.

Thermostat (Compatible Models): Set mode (COOL, OFF), fan (AUTO, ON), and desired temperature. Advanced settings may include compressor delay (anti-short cycle).

Unit Control Board LED: Flashing patterns indicate system status or fault codes (see Diagnostics section).

No User-Adjustable DIP Switches: Settings are managed by the control board logic and thermostat signals.

Connecting to Thermostat & Indoor Unit

Low-voltage control wiring connects outdoor unit to indoor air handler/furnace control board.

  1. Turn off all power to indoor and outdoor units.
  2. At indoor unit control board, identify terminals: Y (cooling), C (common), G (fan), R (24V power).
  3. Run a minimum 18 AWG, 3-conductor thermostat wire (Y, C, R) from indoor board to outdoor unit terminal block.
  4. Connect wires at outdoor terminal block: Y (compressor contactor), C (common), R (24V from indoor).
  5. Ensure connections are secure and wire nuts are used if applicable.

Tip: Use a separate, dedicated low-voltage wire run for the outdoor unit. Do not share this run with the indoor thermostat wire to avoid interference.

Operation & Maintenance

For normal operation, set thermostat to desired temperature. Unit will cycle automatically.

  1. Seasonal Startup: Clear any debris from around unit and coil. Ensure condenser coil is clean.
  2. Routine Operation: Unit runs when thermostat calls for cooling. Fan runs during compressor operation and may continue briefly after compressor shuts off.
  3. Fan Only Mode: Can be selected at thermostat to circulate indoor air without cooling.
  4. Annual Professional Maintenance: Recommended. Includes: check refrigerant charge, inspect electrical components, clean condenser coil, check amp draws, verify safety controls.
  5. Owner Maintenance: Keep area around unit clear of leaves, grass, snow (minimum 24"). Gently clean exterior coil fins with a soft brush or low-pressure water hose (power off).

WARNING! Do not insert fingers or objects into fan grille. Do not use pressure washers on the coil. Always turn off power at the disconnect before performing any maintenance near the unit.

Diagnostics & Alerts

The control board has an LED that flashes to indicate status or lockout conditions.

LED Flash PatternDescriptionPossible Cause
1 FlashNormal OperationUnit is running or on standby.
2 FlashesLoss of Charge / Low PressureRefrigerant leak, restriction, faulty pressure switch.
3 FlashesHigh Pressure LockoutDirty condenser coil, restricted airflow, overcharge, faulty fan motor.
4 FlashesCompressor Overload / OpenElectrical issue, faulty compressor, low voltage.
5 FlashesControl Board FaultPCB communication error or failure.
Continuous OnCall for Cooling PresentThermostat is calling, unit should run.

Reset: Some lockouts auto-reset after a set period (e.g., 1 hour). For persistent faults, power down the unit at the disconnect for 5 minutes, then restore power.

Care & Cleaning

Maintain unit efficiency by keeping it clean and unobstructed.

  1. Exterior Coil: Annually, gently brush debris from fins. Hose from the inside out with low-pressure water to flush dirt. Straighten any bent fins with a fin comb.
  2. Surrounding Area: Keep clear of vegetation, leaves, snow, and storage items.
  3. Cabinet: Wipe with a damp cloth if needed. Do not use harsh chemicals or abrasive cleaners.
  4. Winter (if unused): Consider a waterproof cover to protect from ice and debris, but ensure cover does not trap moisture and is removed before operation.

CAUTION! Always disconnect power before cleaning. Do not use steam or high-pressure sprays. Do not attempt to clean internal electrical components.

Regulatory Information

This product complies with applicable U.S. safety and performance standards. The refrigerant circuit contains R-410A, which is regulated by EPA Section 608. Technicians servicing the refrigerant circuit must be certified. The compressor contains lubricating oil. Dispose of unit in accordance with local regulations. For technical support or to locate a dealer, visit www.americanstandardair.com or contact American Standard Customer Care.

© [Year] American Standard Heating & Air Conditioning. All rights reserved. American Standard is a trademark of American Standard Inc.

Troubleshooting

SymptomPossible CauseCorrective Action
Unit does not startNo power, thermostat setting, safety lockoutCheck disconnect and breaker. Verify thermostat is in COOL, set below room temp. Check for LED fault code.
Fan runs, compressor does notLow refrigerant charge, faulty capacitor, compressor issueCheck pressure switches and refrigerant charge. Test run capacitor. Listen for contactor pull-in.
Compressor short cyclesDirty coil, overcharge, low airflow indoors, faulty pressure controlClean condenser coil. Check refrigerant charge. Verify indoor filter is clean and blower is operating.
Reduced cooling capacityDirty air filter/coil, low refrigerant, restricted ductworkReplace indoor air filter. Clean indoor and outdoor coils. Check system charge and superheat.
Unusual noiseLoose parts, debris in fan, failing motor or compressorTurn unit off. Inspect for loose panels or debris contacting fan. If internal, contact a technician.
Ice on refrigerant lines or indoor coilLow airflow, low refrigerant chargeTurn system OFF. Check/replace air filter. Ensure all supply vents are open. Check for frozen indoor coil. Call for service to check charge.

Note: Many troubleshooting steps involve high voltage and refrigerant. If problem persists, contact a qualified HVAC technician.

Service & Support: For warranty service or dealer location, visit www.americanstandardair.com or call 1-800-428-4326.

American Standard HVAC YCC060F-M Manual © - All Rights Reserved 2025