American Standard HVAC YCC036F-L Manual

The American Standard YCC036F-L is a high-efficiency, single-stage, 3-ton residential condensing unit designed for outdoor installation. It features a scroll compressor, durable weather-resistant cabinet, and compatibility with American Standard indoor units for optimal system performance. Below are key sections for safety, features, installation, setup, operation, and troubleshooting.

1. Features at a Glance 2. Installation 3. First-Time Setup 4. Specifications 5. Controls and Settings 6. Connecting Components 7. Operation 8. Maintenance 9. Regulatory Information 10. Troubleshooting

Features at a Glance

Key components: Weather-resistant galvanized steel cabinet, Scroll compressor, Single-stage operation, High-efficiency coil, Liquid and suction line service valves, Low-pressure switch, High-pressure switch.

FeatureDescription
ModelYCC036F-L (3-ton capacity)
Compressor TypeScroll
StagesSingle-stage cooling
RefrigerantR-410A
CabinetGalvanized steel, painted
Electrical Data208/230V, 1-phase, 60 Hz
Sound RatingQuiet operation design
CoilCorrosion-resistant, enhanced surface
Service ValvesLiquid and suction line access
Safety ControlsLow and high-pressure switches

Installation

Unpack and inspect unit for shipping damage. Select a suitable outdoor location.

  1. Location: Place on a level, stable pad (concrete or composite) with adequate clearance for airflow and service.
  2. Electrical Connection: Disconnect all power. Run properly sized copper wiring from disconnect to unit terminal block per local codes.
  3. Refrigerant Lines: Connect pre-charged, insulated lineset from indoor unit to outdoor service valves. Brazing must be done with nitrogen purge.
  4. Condensate Drain: Ensure indoor unit condensate line is properly installed and routed.
  5. Final Check: Verify all electrical connections are tight, lineset is insulated and secured, and unit is level.

WARNING! Installation must be performed by a qualified HVAC technician. Incorrect installation can cause property damage, personal injury, or death. Handle refrigerant according to EPA regulations.

First-Time Setup

After installation, perform initial startup and system check.

  1. Power On: Restore power at disconnect and indoor air handler/furnace.
  2. Thermostat Setup: Set thermostat to OFF mode. Configure cooling setpoint, fan mode (AUTO recommended).
  3. System Start: Set thermostat to COOL mode and a temperature below room temp. Unit should start after a short delay.
  4. Performance Check: Verify adequate airflow from indoor vents, listen for normal operating sounds, check for unusual vibrations.
  5. Measurements: Technician should verify correct refrigerant charge via subcooling method, electrical amp draw, and temperature split across indoor coil.

CAUTION! Do not operate without proper refrigerant charge. Allow unit to complete a full cycle before adjustments.

Specifications

Controls and Settings

Primary control is via the indoor thermostat. Unit has internal safety and operational controls.

Thermostat: Controls mode (COOL, OFF, FAN), temperature setpoint, and fan operation (AUTO, ON).

Unit Internal Controls: Low-pressure switch (opens on low refrigerant pressure), High-pressure switch (opens on excessive pressure), Compressor contactor, Fan relay, Compressor overload protection.

No user-adjustable settings on outdoor unit. All system adjustments (charge, airflow) must be made by a qualified technician.

Connecting Components

Connects to indoor coil/air handler and thermostat.

  1. Indoor Unit: Matched American Standard evaporator coil or air handler. Connected via refrigerant lineset and low-voltage control wire.
  2. Thermostat: Low-voltage (24V) connection (R, C, Y, G terminals) to control cooling and fan.
  3. Power Supply: Dedicated 230V circuit with disconnect within sight of unit.
  4. Condensate Drain: From indoor unit to suitable drain.

Tip: Use a properly sized lineset. Excessive length or improper sizing reduces efficiency and capacity.

Operation

Normal operation is automatic via thermostat.

  1. Cooling Cycle: When thermostat calls for cooling, it energizes the Y and G terminals. Outdoor fan and compressor start. Indoor blower starts.
  2. Cycle Completion: When set temperature is reached, thermostat de-energizes Y and G. Compressor and outdoor fan stop. Indoor blower may run briefly to utilize remaining coil cooling.
  3. Fan Mode: Setting thermostat fan to ON runs indoor blower continuously for air circulation without cooling.
  4. Off Mode: Thermostat set to OFF prevents cooling cycle.

WARNING! Do not switch thermostat between HEAT and COOL modes rapidly. Allow 5 minutes between mode changes to prevent compressor damage.

Maintenance

Regular maintenance ensures efficiency and longevity. Disconnect all power before servicing.

  1. Outdoor Coil: Keep clean and free of debris (leaves, grass, dirt). Gently clean with a soft brush or low-pressure water hose (power off).
  2. Airflow: Maintain at least 24 inches clearance on all sides, especially around the coil.
  3. Inspect: Periodically check for loose fasteners, damaged insulation on refrigerant lines, or signs of refrigerant leaks.
  4. Professional Service: Schedule annual maintenance by a qualified technician to check refrigerant charge, electrical components, and system performance.

CAUTION! Do not use a pressure washer or harsh chemicals on the coil fins. Do not attempt to repair refrigerant system.

Regulatory Information

This product complies with applicable U.S. safety and performance standards. The refrigerant system contains R-410A, a non-ozone-depleting HFC. Recovery and recycling of refrigerant is required by EPA Section 608 regulations. The compressor contains oil. Dispose of unit in accordance with local ordinances. For support, contact your installing dealer or American Standard Customer Care.

Troubleshooting

SymptomPossible CauseCorrective Action
Unit does not startPower loss, thermostat setting, safety lockoutCheck circuit breaker/disconnect. Verify thermostat is in COOL mode below room temp. Wait 5 minutes for compressor lockout to reset.
Unit runs but does not coolDirty filter/coil, low refrigerant, thermostatReplace indoor air filter. Clean outdoor coil. Contact technician to check charge.
Unit cycles on/off rapidly (short cycles)Dirty filter/coil, overcharge, faulty controlReplace filter. Ensure adequate airflow. Contact technician.
Loud or unusual noiseLoose parts, debris in fan, failing componentTurn unit off. Check for loose panels or debris. Contact technician if noise persists.
Ice on refrigerant lines or coilLow airflow, low refrigerant chargeTurn system OFF. Check/replace air filter. Ensure vents are open. Contact technician.

Reset: Turn thermostat to OFF. Turn off power at disconnect for 1 minute. Restore power and thermostat.

Service: Contact your qualified American Standard dealer. For product information: www.americanstandardair.com

American Standard HVAC YCC036F-L Manual © - All Rights Reserved 2025