American Standard HVAC Odyssey TTA Series Manual

The American Standard Odyssey TTA Series is a high-efficiency, variable-speed air handler designed for use with compatible heat pumps and air conditioners. It features advanced humidity control, quiet operation, durable construction, and compatibility with communicating thermostats for enhanced system performance and comfort. Below are key sections for safety, features, installation, setup, operation, and troubleshooting.

1. Features at a Glance 2. Installation 3. First-Time Setup & Commissioning 4. Specifications 5. Controls and Settings 6. Connecting to System Components 7. Operation Modes 8. Maintenance & Filter Replacement 9. Care & Cleaning 10. Regulatory Information 11. Troubleshooting

Features at a Glance

Key components: Variable-speed ECM blower motor, insulated cabinet, integrated control board, filter rack, drain pan, and connection terminals for thermostat and outdoor unit.

FeatureDescription
Variable-Speed ECM MotorProvides precise airflow control for enhanced comfort and efficiency
Comfort-R™ TechnologyAdvanced humidity control during cooling operation
Quiet OperationInsulated cabinet and low-speed operation for minimal sound
Communicating CapabilityWorks with compatible thermostats for system optimization
Durable ConstructionGalvanized steel cabinet with corrosion-resistant coating
Multi-Position InstallationCan be installed in upflow, downflow, or horizontal configurations
Integrated Control BoardManages blower speed, system communication, and fault diagnostics
Filter AccessEasy-access filter rack for standard 1" to 4" media filters
Drain PanPrimary and secondary condensate removal with safety switch
Service PortsAccess for voltage checks and system diagnostics

Installation

Unpack and inspect contents. Ensure installation location meets clearance requirements.

  1. Select Location: Choose a level, indoor area with proper service clearance (minimum 24 inches front access).
  2. Position Unit: Install in upflow, downflow, or horizontal position per application requirements.
  3. Connect Ductwork: Secure supply and return ducts using appropriate sealing methods.
  4. Electrical Connections: Connect line voltage per wiring diagram (208/230V, 1-phase). Connect low-voltage thermostat wires.
  5. Condensate Drain: Install primary and auxiliary drain lines with proper trap and slope.
  6. Connect to Outdoor Unit: Run refrigerant lineset and connect control wiring to compatible heat pump/AC.

WARNING! Installation must be performed by a qualified HVAC technician in accordance with all local codes and the National Electrical Code. Disconnect all power before servicing.

First-Time Setup & Commissioning

Power on system; configure settings via compatible communicating thermostat.

  1. System Power: Restore electrical power to indoor and outdoor units.
  2. Thermostat Configuration: Follow thermostat prompts to set system type (Heat Pump), stages, and fan control.
  3. Blower Settings: Default CFM settings are programmed. Adjust airflow via thermostat setup menu if required for specific application.
  4. Test Operation: Initiate test modes for cooling, heating, and fan-only to verify correct operation.
  5. Check Drainage: Verify condensate drain is flowing properly.
  6. Final Inspection: Ensure all access panels are secured and area is clean.

CAUTION! Do not jumper R to G to run blower continuously during commissioning. Use thermostat fan settings.

Specifications

Controls and Settings

Primary control is via the system thermostat. Integrated control board manages blower operation.

Thermostat Functions: System Mode (Off, Heat, Cool, Auto, Emergency Heat), Fan (Auto, On, Circulate), Temperature Setpoint, Humidity Setpoint (if equipped), System Status, Alerts.

Control Board LED: Steady green = normal operation. Flashing codes indicate specific status or fault conditions (see Troubleshooting).

Blower Speed Settings: Default cooling/heating CFM is set for matched system. Can be adjusted via compatible thermostat installer setup menu for custom applications (e.g., high static ductwork).

Dehumidification Mode: Activated automatically by communicating thermostat during cooling calls to reduce humidity.

Connecting to System Components

Outdoor Unit: Connect low-voltage control wires (Y, O/B, C, etc.) and refrigerant lines. Thermostat: Connect communicating wires (typically 4-wire). Power: Connect line voltage (L1, L2, Ground). Drain: Connect 3/4" PVC condensate line.

  1. Turn off all power at disconnect and breaker panel.
  2. Match wires to terminal labels on control board (R, C, Y, O/B, etc.).
  3. Ensure refrigerant lines are properly sized, insulated, and leak-checked.
  4. Select correct system mode on thermostat (Heat Pump).

Tip: Refer to the outdoor unit and thermostat installation manuals for specific wiring diagrams and compatibility.

Operation Modes

Operates with compatible heat pump for cooling and heating.

  1. Cooling Mode: Thermostat calls for cooling. Blower operates at cooling CFM. Dehumidification may activate.
  2. Heating Mode: Thermostat calls for heating. Blower operates at heating CFM (typically lower than cooling).
  3. Emergency Heat Mode: Uses backup heat strips (if installed) instead of heat pump.
  4. Fan-Only Mode: Blower circulates air without heating or cooling. Options: ON (continuous), AUTO (with cycle), CIRCULATE (intermittent).
  5. Dehumidification Mode: Blower runs at lower speed during cooling call to enhance moisture removal.
  6. System Shutdown: Thermostat set to OFF. Control board remains powered for potential communication.

WARNING! Do not operate the system without a properly installed air filter. Restricted airflow can damage the unit.

Maintenance & Filter Replacement

Regular maintenance is required for optimal performance and longevity.

  1. Filter: Inspect monthly. Replace 1" filter or clean/replace 4" media filter as needed (typically every 3 months). Slide filter out of rack, insert new one noting airflow direction arrow.
  2. Blower Compartment: Annually, inspect blower wheel for debris and motor for free operation. (Power OFF).
  3. Drain System: Annually, check condensate drain line and pan for algae or blockage. Flush with approved cleaner.
  4. Electrical Connections: Annually (by technician), check tightness of line and low-voltage connections.
  5. General Inspection: Visually inspect cabinet, insulation, and ducts for damage.

CAUTION! Always turn off electrical power at the breaker before performing any maintenance inside the unit.

Care & Cleaning

Exterior: Wipe cabinet with a soft, damp cloth. Do not use harsh chemicals or abrasives.

CAUTION! Do not spray water or cleaners into electrical compartments, control board, or motor. Do not attempt to lubricate the ECM motor.

Regulatory Information

This product complies with applicable U.S. safety and performance standards. It is designed for use in the United States and Canada. The ECM motor complies with U.S. Department of Energy regulations for energy efficiency. For technical support or to locate a dealer, visit www.americanstandard.com or contact American Standard Customer Care at 1-800-526-2200.

Troubleshooting

SymptomPossible CauseCorrective Action
No power to unit (no LED)Breaker tripped, disconnect off, loose wireCheck breaker and disconnect switch. Verify line voltage at unit.
Blower not running (LED steady)Thermostat call missing, filter blockedVerify thermostat setting and call. Check for extremely dirty filter.
Blower not running (LED flashing)Control board fault codeCount flashes: 2=Pressure switch, 3=Indoor temp sensor, 4=Communication error. Refer to service manual.
Poor airflowDirty filter, closed registers, high static pressureReplace filter. Ensure supply/return registers are open. Check for blocked ducts.
Water leakageClogged drain line, misaligned drain panClear primary drain line. Check secondary drain. Ensure unit is level.
Unusual noiseLoose panel, debris in blower, duct vibrationTighten access panels. Inspect blower wheel for debris. Secure duct connections.
No communication with thermostatIncorrect wiring, incompatible thermostatVerify wiring at control board (R, C terminals). Ensure a compatible communicating thermostat is used.

Reset: Power cycle unit (turn breaker off for 30 seconds, then on). If problem persists, call for service.

Service: Contact a qualified American Standard dealer. For support: 1-800-526-2200; www.americanstandard.com

American Standard HVAC Odyssey TTA Series Manual © - All Rights Reserved 2025