American Standard HVAC 5A7A7060A1000A Manual

The American Standard 5A7A7060A1000A is a high-efficiency residential air conditioning system designed for reliable cooling performance. This manual covers the 5A7A7060A1000A model, which features a single-stage compressor, durable corrosion-resistant components, compatibility with various thermostats, and is designed for use with matching American Standard indoor units. Below are key sections for safety, features, installation, setup, operation, maintenance, and troubleshooting.

1. Features at a Glance 2. Installation Requirements 3. First-Time Setup & Startup 4. Specifications 5. Controls and Operation 6. Connecting to Thermostat & Indoor Unit 7. Maintenance Procedures 8. Safety Features 9. Care & Cleaning 10. Regulatory Information 11. Troubleshooting

Features at a Glance

Key components: Outdoor Condenser Unit, Compressor, Coil, Fan Motor, Electrical Connections, Service Valves.

FeatureDescription
High-Efficiency Scroll CompressorProvides quiet, reliable, and efficient cooling operation
Corrosion-Resistant CabinetGalvanized steel with powder coat paint for durability
Sound Reduction DesignIsolated compressor compartment and fan design for quieter operation
Service ValvesFront-access liquid and suction valves for easier servicing
Electrical DisconnectRequires field-supplied disconnect within sight of unit
RefrigerantUses R-410A refrigerant
Compatible Indoor UnitsDesigned for use with matching American Standard air handlers or furnaces
Single-Stage OperationProvides consistent cooling capacity
Thermostat CompatibilityWorks with most 24V single-stage thermostats
Safety SwitchesIncludes high and low-pressure switches, compressor overload protection

Installation Requirements

Unpack and inspect unit for shipping damage. Select a suitable outdoor location.

  1. Location: Place on a level, stable pad (concrete or composite) with adequate clearance for airflow and service (min 24" on all sides, 48" above).
  2. Electrical Connection: Connect to proper power supply (208/230V, 1-phase, 60Hz) via a field-supplied weatherproof disconnect. Follow local codes.
  3. Refrigerant Lines: Connect properly sized and insulated copper lineset between outdoor unit and indoor coil. Brazing with nitrogen purge is required.
  4. Condensate Drain: Ensure indoor unit drain line is properly installed and trapped.
  5. Final Check: Verify all electrical connections are tight, lineset is sealed, and unit is level.

WARNING! Installation must be performed by a qualified HVAC technician in accordance with national and local codes. Incorrect installation can cause property damage, personal injury, or death. Disconnect all power before servicing.

First-Time Setup & Startup

After installation, perform startup and system check.

  1. Power On: Turn on power at disconnect and indoor unit.
  2. Thermostat Setup: Set thermostat to OFF. Configure for conventional single-stage cooling (if programmable).
  3. Startup Procedure: Technician must: Check refrigerant charge via subcooling method, measure voltage and amperage, verify fan operation, check temperature drop across indoor coil (typically 15-20°F).
  4. System Check: Listen for abnormal noises, verify condensate is draining, ensure thermostat calls for cooling correctly.

CAUTION! Only a qualified technician should perform startup and charging procedures. Incorrect refrigerant charge will reduce efficiency and can damage the compressor.

Specifications

Controls and Operation

Primary control is via the indoor thermostat. Unit has an internal control board for protection and sequencing.

Thermostat Operation: Set to COOL and desired temperature. Fan can be set to AUTO (runs only with cooling) or ON (continuous).

Unit Sequence: On a call for cooling, thermostat energizes the contactor in the outdoor unit. Compressor and fan start after a brief time delay. When thermostat is satisfied, contactor de-energizes and unit shuts off.

LED Status Light: The control board may have an LED that flashes a code to indicate normal operation or fault conditions (see Troubleshooting).

Connecting to Thermostat & Indoor Unit

Low-voltage connections (24V) are made at the indoor air handler/furnace control board.

  1. Turn OFF all power to indoor and outdoor units.
  2. At indoor unit control board, connect: R (24V power), C (Common), Y (Compressor/Cooling), G (Fan).
  3. Run low-voltage thermostat wire from indoor board to outdoor unit. Connect Y and C terminals at outdoor unit contactor/board.
  4. Ensure high-voltage connections (L1, L2) are made at the outdoor unit disconnect and contactor.

Tip: Refer to the wiring diagram located on the inside of the outdoor unit service panel for specific terminal designations.

Maintenance Procedures

Regular maintenance is required for efficiency and longevity. Some tasks are homeowner-friendly; others require a technician.

  1. Homeowner (Monthly/Seasonally): Keep area around unit clear of leaves, grass, shrubs (min 24"). Visually inspect for obvious damage or debris on coil.
  2. Technician (Annual): Clean condenser coil with appropriate cleaner and water (from inside out). Check refrigerant charge. Inspect electrical connections for tightness and corrosion. Check fan motor and blades. Lubricate motors if required (check specifications). Check and clean indoor coil and drain line.
  3. Filter Maintenance: Replace or clean indoor air filter monthly during cooling season. A dirty filter reduces airflow and efficiency.

WARNING! Always turn off power at the disconnect before performing any maintenance near the unit. Do not attempt to clean coil with high-pressure water as it can bend fins.

Safety Features

High-Pressure Switch: Opens circuit if discharge pressure is too high. Low-Pressure Switch: Opens circuit if suction pressure is too low. Compressor Overload: Internal protector. Time Delay: Prevents short cycling (approx. 5-minute delay after shutdown).

Care & Cleaning

Keep the outdoor coil clean. Gently rinse with a garden hose (power off) to remove loose dirt. For heavy dirt, a technician should use coil cleaner. Keep the top of the unit free of debris. Do not use the unit as a shelf.

CAUTION! Do not use sharp objects to clean fins. Do not use harsh chemicals. Ensure unit is level to allow proper condensate drainage from the indoor coil.

Regulatory Information

This product complies with applicable U.S. safety and performance standards. The refrigerant used (R-410A) is regulated by the EPA; only certified technicians may service the sealed refrigerant system. Proper disposal is required at end of life. For support, contact your local American Standard dealer or visit www.americanstandardair.com. This equipment is designed for residential use.

Troubleshooting

SymptomPossible CauseCorrective Action
Unit does not startPower off, thermostat setting, tripped breaker, time delayCheck disconnect and breaker. Ensure thermostat is set to COOL below room temp. Wait 5 minutes after previous cycle.
Unit runs but does not coolDirty filter, dirty coils, low refrigerant, thermostat issueReplace indoor filter. Check for blocked outdoor coil. Call technician to check charge.
Unit cycles on/off rapidly (short cycles)Dirty filter/coil, overcharge/undercharge, faulty sensorCheck and clean filter/coil. Call technician to diagnose refrigerant charge or controls.
Loud or unusual noiseDebris in fan, loose parts, failing motor or compressorTurn unit off. Check for and remove debris. If noise persists, call technician.
Ice on refrigerant lines or indoor coilLow airflow (dirty filter/coil), low refrigerant chargeTurn system OFF. Let ice melt. Replace filter. If problem returns, call technician.
LED flashing a codeLockout or fault conditionCount flashes, refer to fault code chart inside service panel. Call technician.

Reset: Turning power off at disconnect for 1 minute may reset some fault lockouts. If problem persists, call for service.

Service: Contact your local American Standard dealer. For product information: www.americanstandardair.com.

American Standard HVAC 5A7A7060A1000A Manual © - All Rights Reserved 2025