The American Standard 4TXM2118A12N0A is a high-efficiency, single-stage, 18 SEER air conditioner condenser unit designed for residential use. It features a durable WeatherArmor™ Ultra protection system, Spine Fin™ coil technology for enhanced heat transfer, low sound operation, compatibility with American Standard communicating thermostats, and is engineered to work with matching indoor units for optimal performance. Below are key sections for safety, features, installation, setup, operation, maintenance, and troubleshooting.
Key components: Durable outdoor cabinet with Spine Fin™ coil, Compressor with sound insulation, Electrical connection box, Service valves, and Fan assembly.
| Feature | Description |
|---|---|
| WeatherArmor™ Ultra Cabinet | Galvanized steel with baked-on powder paint for corrosion resistance |
| Spine Fin™ Coil | All-aluminum microchannel coil for efficient heat transfer and durability |
| Single-Stage Climatuff® Compressor | Reliable operation with sound-dampening insulation |
| Low Sound Operation | Designed for quiet outdoor performance |
| Communicating Capability | Compatible with American Standard AccuLink™ communicating thermostats (when paired with compatible indoor unit) |
| Service Valves | Front-access for easier installation and service |
| High Static Fan | Provides consistent airflow in various conditions |
| 18 SEER Rating | High seasonal energy efficiency ratio for energy savings |
| R-410A Refrigerant | Environmentally responsible refrigerant |
| Factory Installed Filter-Drier | Protects system from moisture and contaminants |
Unpack and inspect unit for shipping damage. Select a suitable location.
WARNING! Installation must be performed by a qualified HVAC technician in accordance with all local, state, and national codes. Incorrect installation can cause property damage, personal injury, or death. Handle refrigerant responsibly.
Do not energize unit until all installation steps are complete and verified.
CAUTION! Never start the unit with service valves closed. Do not bypass safety devices. Record all commissioning data (voltages, amperages, pressures, temperatures) for future reference.
Primary control is via the indoor thermostat. Unit has an internal control board with LED status light.
Thermostat Operation: Set to COOL mode and desired temperature. Fan can be set to AUTO (cycles with compressor) or ON (continuous).
Unit Status LED: Located on control board inside service panel. Flash patterns indicate normal operation or fault conditions (see Troubleshooting section).
Safety Controls: Unit includes high-pressure switch, low-pressure switch, compressor overload, and anti-short cycle timer (typically 5 minutes).
Communicating Systems: If paired with an AccuLink indoor unit and thermostat, the system performs automatic configuration, diagnostics, and advanced staging for efficiency and comfort.
This unit must be paired with an approved American Standard indoor coil or air handler.
Tip: Always refer to the installation instructions for the specific indoor unit model for correct wiring and setup details.
Homeowner (Annual):
Qualified Technician (Annual):
High & Low Pressure Switches: Protect compressor from abnormal system pressures.
Compressor Overload Protector: Internal protection against overheating.
Anti-Short Cycle Timer: Prevents compressor from restarting for approximately 5 minutes after shutdown to protect it.
Fused Disconnect Required: A field-supplied fused disconnect switch must be installed within sight of the unit per electrical code.
Outdoor Coil: Turn OFF power at the disconnect. Remove large debris by hand. Use a soft brush or low-pressure water spray from the inside of the coil facing out to wash away dirt. Do not use a pressure washer as it can bend fins.
Cabinet: Wipe with a damp cloth. Do not use harsh chemicals or abrasive cleaners.
CAUTION! Always disconnect power before performing any cleaning or maintenance. Do not attempt to straighten coil fins with a sharp object. Keep the top grille (fan guard) in place at all times.
This product complies with applicable U.S. safety and performance standards. The refrigerant, R-410A, is subject to EPA regulations (Section 608). Technicians must be certified to service this equipment. Proper recovery and recycling of refrigerant is required by law. This unit contains materials that may be recyclable. Check local ordinances for disposal. For technical support or warranty service, contact your installing American Standard dealer or visit www.americanstandardair.com.
NOTE: Most repairs should be performed by a qualified HVAC technician.
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| Unit does not start | Power off, tripped breaker, blown fuse, thermostat setting, anti-short cycle delay. | Check disconnect and breaker. Ensure thermostat is in COOL mode set below room temp. Wait 5 minutes. Check for clogged filter or dirty indoor coil restricting airflow. |
| Unit runs but does not cool | Dirty filter/coils, low refrigerant, faulty compressor. | Replace air filter. Clean indoor and outdoor coils. Have technician check refrigerant charge and compressor operation. |
| Unit cycles on/off frequently (short cycles) | Dirty filter/coil, low refrigerant, oversized unit, thermostat location. | Clean or replace filter. Clean coils. Have technician check charge. Ensure thermostat is not in direct sunlight or near heat sources. |
| Loud or unusual noise | Loose parts, debris in fan, failing motor or compressor. | Turn unit off. Check for and remove debris. Tighten access panels. Contact technician if noise persists. |
| Ice on refrigerant lines or outdoor unit | Low airflow (dirty filter/coil), low refrigerant charge. | Turn system OFF (use FAN only to melt ice). Replace filter. Clean indoor coil. Have technician check for refrigerant leak and proper charge. |
| Status LED flashing a code | System fault (e.g., pressure switch open, communication error). | Count flashes and refer to fault code chart on unit panel or installation manual. Contact a qualified technician for diagnosis. |
Reset: Turning power off at the disconnect for 5 minutes may reset internal fault lockouts. If problem persists, call for service.
Service: Contact your local American Standard dealer. For product information: www.americanstandardair.com.