American Standard HVAC 4A7L6018A1000A Manual

The American Standard 4A7L6018A1000A is a high-efficiency, single-stage, 18 SEER residential air conditioner with a 5-ton cooling capacity. It features a durable, weather-resistant cabinet, a scroll compressor for quiet operation, a high-efficiency coil, a factory-installed filter drier, and a low-pressure switch for protection. Designed for use with matched indoor units, it operates on 208/230V AC, 1-phase, 60Hz power. Below are key sections for safety, features, installation, setup, operation, maintenance, and troubleshooting.

1. Features at a Glance 2. Installation 3. First-Time Setup & Startup 4. Specifications 5. Controls and Settings 6. Connecting to Indoor Unit & Thermostat 7. Operating Instructions 8. Maintenance Procedures 9. Regulatory Information 10. Troubleshooting

Features at a Glance

Key components: Weather-resistant galvanized steel cabinet, Scroll Compressor, High-Efficiency Coil, Liquid Line Filter Drier, Low-Pressure Switch, Service Valves, Electrical Disconnect (field supplied).

FeatureDescription
Scroll CompressorProvides quiet, reliable, and efficient operation
High-Efficiency CoilEnhanced surface design for optimal heat transfer
Liquid Line Filter DrierFactory-installed to protect system from moisture and debris
Low-Pressure SwitchProtects compressor from operating under low refrigerant charge conditions
Service ValvesFor system charging, evacuation, and pressure measurement
CabinetGalvanized steel with powder-coat paint for corrosion resistance
Electrical Requirements208/230V, 1 Phase, 60 Hz
RefrigerantR-410A
Cooling Capacity5 Tons (60,000 BTU/H)
SEER RatingUp to 18 SEER

Installation

Unpack and inspect unit for shipping damage. Select a level, stable outdoor location with adequate clearance for airflow and service.

  1. Positioning: Place on a solid, level pad (concrete recommended) away from windows, shrubbery, and where noise or condensate drainage could be a nuisance.
  2. Electrical Connection: Install a field-supplied weatherproof electrical disconnect within sight of the unit. Connect power leads (L1, L2) and ground per local codes and unit wiring diagram.
  3. Refrigerant Lines: Connect pre-charged, insulated refrigerant lines (liquid and suction) from the matched indoor unit. Brazing must be done with nitrogen purge to prevent oxidation.
  4. Condensate Drain: Ensure indoor unit condensate drain line is properly installed and routed.
  5. Thermostat Wiring: Connect low-voltage control wires (typically 24V) from the indoor air handler/furnace to the outdoor unit's control terminal strip.

WARNING! Installation and service must be performed by a qualified HVAC technician in accordance with all national and local codes. Incorrect installation can cause property damage, personal injury, or death. Disconnect all power before servicing.

First-Time Setup & Startup

After installation is complete, perform initial system startup and checkout.

  1. Pre-Start Check: Verify all electrical connections are tight. Ensure refrigerant line service valves are fully open. Check that the indoor unit filter is clean.
  2. Power On: Turn on power at the disconnect and indoor unit.
  3. Thermostat Setup: Set thermostat to OFF mode. Configure thermostat settings (cooling setpoint, fan mode AUTO/ON) as desired.
  4. System Start: Set thermostat to COOL mode and a temperature below room temperature. The indoor blower and outdoor fan/compressor should engage.
  5. Performance Check: Listen for unusual noises. Check that cool air is delivered from indoor vents. Measure system operating pressures and superheat/subcooling to verify correct charge.

CAUTION! Do not operate the system without adequate refrigerant charge. Allow the unit to run for at least 15 minutes to stabilize before taking measurements.

Specifications

Controls and Settings

Primary control is via the connected thermostat. The outdoor unit contains a control board with LED status indicators and protective devices.

Thermostat: Controls system mode (OFF, COOL, HEAT*, FAN), temperature setpoint, and fan operation (AUTO, ON). *Heating requires a matched heat pump model or separate furnace.

Outdoor Unit Controls: - Compressor Contactor: Engages compressor and outdoor fan. - Control Board: Manages safeties and compressor operation. Includes diagnostic LEDs. - Protective Devices: High-pressure switch, low-pressure switch, compressor overload, time-delay relay (typically 5 minutes).

Settings: Most operational settings (fan speed, temperature differential) are configured at the indoor air handler or thermostat. No user-adjustable settings are on the outdoor unit itself.

Connecting to Indoor Unit & Thermostat

This unit must be connected to a matched American Standard indoor coil and air handler or furnace.

  1. Turn off all power to indoor and outdoor units at the disconnects.
  2. Run properly sized, insulated refrigerant lineset between outdoor and indoor units.
  3. Connect the liquid (small) and suction (large) lines to the service valves. Use a torque wrench.
  4. Run a 24V control cable (minimum 18 AWG, 3-conductor recommended) from the indoor unit control board to the outdoor unit's terminal strip (typically labeled Y, C, O/B for heat pump, G for fan).
  5. Connect the thermostat wires to the indoor unit control board per the indoor unit's wiring diagram.

Tip: Label all wires during installation for easier future service. Always refer to the specific wiring diagrams provided with the indoor unit.

Operating Instructions

Operation is simple via the wall thermostat.

  1. Cooling Mode: Set thermostat to COOL. Set desired temperature. The system will cycle on and off automatically to maintain setpoint.
  2. Fan Mode: Set to AUTO for the blower to run only with cooling cycles. Set to ON for continuous air circulation.
  3. Shutting Off: Set thermostat to OFF.
  4. Seasonal Shutdown: For winter in cooling-only applications, turn off power at the outdoor disconnect. Covering the unit is optional but can protect from debris.

WARNING! Do not set the thermostat to a temperature drastically below the outdoor temperature for extended periods, as this may cause the indoor coil to freeze. Do not block supply or return air vents indoors.

Maintenance Procedures

Homeowner (Monthly/Seasonally): - Keep the outdoor unit clear of leaves, grass clippings, snow, and shrubs (maintain 24" clearance). - Replace or clean the indoor air filter every 1-3 months. - Ensure condensate drain line is clear.

Professional Technician (Annually): - Inspect electrical connections for tightness and corrosion. - Clean outdoor coil with a fin comb and gentle water spray (power off). - Check refrigerant charge and system operating pressures. - Inspect and clean indoor coil if accessible. - Check blower motor and wheel. - Verify all safety controls function properly.

CAUTION! Homeowners should only perform basic cleaning and filter changes. All other maintenance must be done by a qualified technician.

Regulatory Information

This product complies with applicable U.S. safety and performance standards. It contains R-410A refrigerant, which must be recovered by EPA-certified technicians. The scroll compressor contains lubricating oil. Proper disposal is required per local regulations. This product is designed for use in the United States and Canada. For technical support or warranty service, contact your installing American Standard dealer or visit www.americanstandardair.com.

Troubleshooting

SymptomPossible CauseCorrective Action
Unit does not startPower off, tripped breaker, thermostat setting, time delayCheck disconnects and breakers. Verify thermostat is in COOL mode below room temp. Wait 5 minutes for time delay.
Unit runs but does not coolDirty filter, blocked coils, low refrigerantReplace indoor filter. Clear debris from outdoor coil. Call technician to check charge.
Unit cycles on/off frequently (short cycles)Dirty filter/coil, improper charge, oversized unitClean filter/coil. Call technician to diagnose charge or sizing issue.
Ice on refrigerant lines or indoor coilLow airflow (dirty filter/coil, bad blower), low refrigerantTurn system OFF. Replace filter. Call technician once ice melts to check airflow and charge.
Unusual noise (rattling, grinding)Loose panels, debris in fan, failing motor or compressorTurn unit OFF. Check for loose screws/panels. Clear visible debris. If noise persists, call technician.
Water leakage indoorsClogged condensate drain lineClear the drain line. A wet/dry vacuum can be used on the drain port outside.

Reset: If a safety lockout occurs, turn off power at the disconnect for 30 seconds, then restore power.

Service: For all technical issues beyond basic homeowner checks, contact your qualified American Standard HVAC dealer.

American Standard HVAC 4A7L6018A1000A Manual © - All Rights Reserved 2025