The American Standard 4A7L5024N1000A is a high-efficiency, single-stage, 2-ton air conditioning condenser unit designed for residential use. It features a durable, weather-resistant cabinet, a scroll compressor for quiet operation, a Spine Fin™ coil for efficient heat transfer, and compatibility with American Standard communicating thermostats for enhanced system control. Below are key sections for safety, features, installation, setup, operation, maintenance, and troubleshooting.
Key components: Weather-resistant galvanized steel cabinet, Scroll compressor, Spine Fin™ coil, Liquid and suction line service valves, High and low-pressure switches, Fan motor with permanent capacitor.
| Feature | Description |
|---|---|
| Cabinet | Galvanized steel with powder-coat paint for corrosion resistance |
| Compressor | Single-stage scroll type for reliability and low sound levels |
| Coil | Spine Fin™ aluminum for improved heat transfer and durability |
| Fan Motor | Permanent split capacitor (PSC) type |
| Refrigerant | R-410A |
| Electrical Connection | Weatherproof disconnect box (field supplied) |
| Service Valves | Liquid line and suction line access ports |
| Sound Insulation | Compressor compartment blanket for quiet operation |
| Compatibility | Designed to match with American Standard indoor coils and air handlers |
| Communications | Optional communicating capability with compatible thermostats |
Unpack and inspect unit for shipping damage. Select a suitable outdoor location.
WARNING! Installation must be performed by a qualified HVAC technician in accordance with all local codes and the National Electrical Code (NEC). Incorrect installation can cause property damage, personal injury, or death. Disconnect all power before servicing.
Power on system; follow startup procedure.
CAUTION! Do not operate the unit without the service panels securely in place. Keep the area around the unit clear of debris and vegetation.
Primary control is via the indoor thermostat. Unit has internal safeties (high/low pressure switches, compressor overload).
Thermostat Functions: MODE (Cool/Off/Heat*), FAN (Auto/On), TEMPERATURE SETPOINT. *Heating requires a matched furnace or heat pump.
LED Status Light (on control board): Steady ON = normal operation. Flashing patterns indicate specific fault codes (see Troubleshooting section).
Service Valve Positions: Back-seated (fully counterclockwise) for normal operation. Front-seated (fully clockwise) for system pump-down or service.
Low-voltage connection (typically 24VAC) between indoor air handler/furnace, thermostat, and outdoor unit.
Tip: Refer to the wiring diagram located on the inside of the outdoor unit's service panel and the indoor unit's installation manual for specific terminal designations.
Unit cycles automatically based on thermostat demand.
WARNING! Do not attempt to manually operate contactors or service valves while unit is energized. Do not spray water on the unit while it is running.
Homeowner (Monthly/Seasonally):
Professional Technician (Annually):
This product complies with applicable U.S. safety and performance standards. The 4A7L5024 unit is covered by a limited warranty. The compressor has a separate limited warranty. Registration is required for full warranty benefits; see warranty certificate included with the unit or register online at www.americanstandardair.com. For technical support or to locate a dealer, visit the website or contact American Standard Heating & Air Conditioning at 1-800-428-4326.
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| Unit does not start | Power loss, thermostat setting, tripped breaker/blown fuse | Check thermostat is in COOL and set below room temp. Check disconnect switch and circuit breaker. Reset if tripped. Call for service if problem persists. |
| Outdoor fan runs, compressor does not | Internal overload, low pressure switch open, faulty capacitor | Wait 30 minutes for compressor overload to reset. If it doesn't start, call for service. |
| Unit cycles on/off frequently (short cycles) | Dirty air filter, dirty coil, low refrigerant, thermostat location | Replace air filter. Clean indoor and outdoor coils if dirty. Call for service to check charge. |
| Reduced cooling/airflow | Dirty filter, blocked registers, dirty evaporator coil, low refrigerant | Replace filter. Ensure supply/return vents are open/unblocked. Call for service. |
| Ice on refrigerant lines or indoor coil | Dirty filter, low airflow, low refrigerant charge | Turn system OFF at thermostat. Replace filter. Allow ice to melt completely. Call for service. |
| LED flashing a code | System fault detected | Count flashes, refer to fault code chart inside service panel. Call for service and report code. |
Reset: For lockout conditions, turn thermostat to OFF, turn off power at disconnect for 30 seconds, then restore power and reset thermostat.
Service: For all technical issues, contact a qualified American Standard dealer. 1-800-428-4326; www.americanstandardair.com