The American Standard 4A6V0036A1000B is a high-efficiency residential air conditioning unit with a nominal cooling capacity of 3 tons (36,000 BTU/h), featuring R-410A refrigerant, single-phase power supply, and compatibility with variable-speed air handlers. Designed for quiet operation and energy efficiency, this unit includes advanced diagnostics, corrosion-resistant components, and smart thermostat compatibility. Below are key sections for safety, features, installation, setup, operation, maintenance, and troubleshooting.
Key components: Outdoor condenser unit, compressor, coil, fan motor, electrical connections, service valves, and diagnostic LED.
| Feature | Description |
|---|---|
| Compressor | Scroll type with sound insulation for quiet operation |
| Refrigerant | R-410A, environmentally friendly |
| Coil | Corrosion-resistant copper tube with aluminum fins |
| Fan Motor | Permanent split capacitor (PSC) with adjustable speed |
| Electrical Box | Weatherproof with terminal connections |
| Service Valves | Liquid and vapor line access ports |
| Diagnostic LED | Flashing codes for system status and faults |
| Sound Level | Low decibel rating for residential use |
| Compatibility | Works with American Standard variable-speed air handlers |
| Warranty | Limited parts warranty (see documentation) |
Unpack and inspect unit for damage. Select location with proper clearance.
WARNING! Installation must be performed by qualified HVAC technician. Disconnect power before servicing.
After installation, power on system and configure settings.
CAUTION! Do not operate without proper refrigerant charge. Ensure all access panels are secured.
Primary control via thermostat; unit has internal diagnostics and dip switch settings.
Thermostat Functions: Mode (COOL, HEAT, OFF, AUTO), Fan (AUTO, ON), Temperature setpoint, Schedule programming.
Unit Controls: Service valve positions (front-seated, back-seated, mid-position), electrical disconnect switch.
Diagnostic LED Patterns: Steady on = normal operation; Slow flash = standby; Rapid flash = fault condition (refer to code chart).
Dip Switches: For technician use only - adjust fan delay, compressor protection, etc.
Compatible with most 24V thermostats; requires C-wire for proper operation.
Tip: Use a programmable thermostat for optimal energy efficiency.
Unit operates based on thermostat signals.
Normal Operation Sounds: Compressor hum, fan airflow, refrigerant flow hiss, clicking during startup/shutdown.
Regular maintenance ensures efficiency and longevity.
| Maintenance Task | Frequency | Procedure |
|---|---|---|
| Filter replacement | Monthly | Replace indoor air filter (size depends on air handler) |
| Coil cleaning | Annually | Clean outdoor coil with gentle water spray (power off) |
| Clear debris | Seasonally | Remove leaves, grass from around unit |
| Inspect electrical | Annually | Check connections for tightness (qualified technician) |
| Check refrigerant | As needed | Verify charge with gauges (qualified technician only) |
Turn off power before any cleaning. Keep area around unit clear.
CAUTION! Never insert objects into fan or coil. Do not use pressure washer.
UL listed; meets DOE efficiency standards. Refrigerant handling requires EPA Section 608 certification. Manufactured to comply with ASHRAE standards. Copyright © American Standard Heating & Air Conditioning. For support, visit www.americanstandardair.com or contact 1-800-628-4516. Keep this manual for future reference.
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| Unit not running | Power loss, thermostat setting | Check disconnect switch; verify thermostat set to COOL below room temp. |
| Poor cooling | Dirty filter, low refrigerant | Replace filter; contact technician for refrigerant check. |
| Loud noises | Debris in fan, loose parts | Turn off power; remove debris; tighten access panels. |
| Ice on coils | Low airflow, low charge | Check filter; ensure vents open; call technician. |
| Fan not running | Motor capacitor, obstruction | Power off; check for obstruction; capacitor replacement by technician. |
| LED flashing rapidly | System fault | Count flashes: 2 = low pressure; 3 = high pressure; 4 = compressor fault; call technician. |
Reset Procedure: Turn off thermostat, turn off disconnect switch, wait 5 minutes, restore power in reverse order.
Service: 1-800-628-4516; www.americanstandardair.com