The American Standard 2A7A3018-060A1000A is a high-efficiency residential air conditioning system with a nominal cooling capacity of 60,000 BTU/hr (5 tons), featuring a single-stage scroll compressor, R-410A refrigerant, corrosion-resistant coil, low-sound operation, and compatibility with variable-speed air handlers. Designed for 208/230V AC, 60Hz operation. Below are key sections for safety, features, installation, setup, operation, maintenance, and troubleshooting.
Key components: Outdoor condensing unit with scroll compressor, coil, fan motor, electrical connections, and service valves.
| Feature | Description |
|---|---|
| Compressor | Single-stage scroll compressor for reliable operation |
| Refrigerant | R-410A, environmentally friendly |
| Coil | Corrosion-resistant copper tube/aluminum fin |
| Fan Motor | Permanent split capacitor (PSC) motor |
| Sound Level | Low-sound operation for quiet performance |
| Electrical | 208/230V AC, 1-phase, 60Hz |
| Service Valves | Liquid and suction line valves for installation/service |
| Dimensions | Compact outdoor unit design |
| Compatibility | Works with variable-speed air handlers for enhanced efficiency |
| Warranty | Limited parts warranty (see manual for details) |
Unpack and inspect unit for damage. Ensure proper location and clearances.
WARNING! Installation must be performed by a qualified HVAC technician. Follow all local codes. Risk of electric shock and refrigerant exposure.
After installation, perform initial startup and system check.
CAUTION! Do not operate without proper refrigerant charge. Allow unit to stabilize for 10-15 minutes after startup.
Primary control via compatible thermostat (not included). Unit has internal safeties and control board.
Thermostat Functions: Mode (COOL, OFF, FAN), Temperature Setpoint, Fan (AUTO, ON).
Unit Control Board: LED status light (green = normal, flashing = fault code). Compressor short-cycle protection (5-minute delay). High/low pressure switches. Overload protection for compressor and fan motor.
Settings via Thermostat: Adjust temperature differential (if programmable). Set fan operation. Program schedules for energy savings.
Compatible with most 24VAC thermostats. Requires proper wiring to indoor air handler.
Tip: Use 18-gauge thermostat wire. Ensure connections are tight and correct per wiring diagram.
Operates in COOL mode only (cooling-only unit). Fan can run continuously or auto.
WARNING! Do not operate in heating mode. Unit is cooling-only. Operating below 55°F ambient may cause coil freeze-up.
Regular maintenance ensures efficiency and longevity. Perform annually or as needed.
CAUTION! Disconnect power before servicing. Coil cleaning chemicals may be harmful; follow manufacturer instructions.
UL Listed. Complies with DOE energy efficiency standards. Refrigerant handling requires EPA Section 608 certification. Manufactured to meet AHRI performance standards. Copyright © American Standard Heating & Air Conditioning. For support, visit www.americanstandardair.com or contact 1-800-628-4516.
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| Unit not running | Power, thermostat, delay | Check disconnect and breaker. Verify thermostat setting and batteries. Wait 5 minutes for delay. |
| Poor cooling | Dirty filter/coil, low charge | Replace filter. Clean outdoor coil. Check refrigerant charge (call technician). |
| Unit cycles on/off rapidly | Dirty coil, airflow, overcharge | Clean coils. Check indoor blower and filter. Verify charge. |
| Ice on outdoor unit | Low airflow, low charge | Check indoor filter and blower. Ensure registers open. Check charge. |
| Unusual noise | Debris, loose parts, fan | Clear debris from fan. Tighten access panels. Inspect fan blade for damage. |
| LED flashing code | Fault condition | Count flashes: 2 = low pressure, 3 = high pressure, 4 = compressor overload, etc. Refer to manual. |
Reset: Turn thermostat to OFF, then back to COOL. If fault persists, power cycle at disconnect.
Service: 1-800-628-4516; www.americanstandardair.com